Application: | Commercial |
---|---|
Certification: | UL, ISO9001, CE |
Type: | Valve |
Transport Package: | Carton |
Specification: | electronic type |
Trademark: | Sanhua |
Customization: |
---|
Suppliers with verified business licenses
GENERAL SPECIFICATIONS
Applicable for all common HFC, HFO refrigerants such as: R134a, R404A, R407A/F, R407C, R410A, R448A, R449A, R450A, R452A, R513A, R507A1)
Cooling capacity: 3,5 to 105 kW (R22 nominal capacity)
500 steps (full stroke); 32 ± 20 opening steps
Medium temperature TS min./max.: -30°C /+70°C (duty cycle rate below 50%)
Ambient temperature min./max.: -30°C / +60°C (duty cycle rate below 50%)
Relative humidity: : 0 to 95% RH • Installation position:
- Coil installed in the upwards position, valve rotor central axis within ±15° versus vertical axis
- Inlet connection preferably sidewise, outlet preferably downwards
Certifications: UL/CSA and declaration according to LVD or PED
Note: 1) Flammable refrigerants like R32, R290, R1234ze(E), R1234yf on request
ELECTRICAL PARAMETERS
Rated voltage: 12V DC(± 10%), rectangular wave
Actuating mode: 4-phase 8-step permanent magnet stepping motor of direct-acting type
Excitation mode: 1 ~ 2 phase excitation, monopole actuation
• Excitation rate:
- Seat Ø 1,3 to 3,2 mm: 30 to 90pps
- Seat Ø 4,0 to 6,5 mm: 30 to 40pps
• Activation of self-holding mechanism: Maintain excitation in stop position min. 0,1~1,0 sec.
• Min. motion time from completely open to completely closed: - Seat Ø 1,3 to 3,2 mm: 6s @ 90pps• Coil current:
- Seat Ø 1,3 to 3,2 mm: 260mA/phase (20°C) - Seat Ø 4,0 to 6,5 mm: 375mA/phase (20°C)
• Coil resistance:
- Seat Ø 1,3 to 3,2 mm: 46 ± 3.7 Ω/phase (20°C) - Seat Ø 4,0 to 6,5 mm: 32 ± 3.2 Ω/phase (20°C)
• Insulation class of coil: E • Protection class: IP 67
Suppliers with verified business licenses