Expansion Valve
Specifications:
1.Wide range of evaporation temperature;
2.Use with R22,R134A,R404A,R507,R407C&R502;
3.Max.testing pressure: 36bar, Allow working pressure: 28bar;
Expansion Valve - R2 Series
Model |
refrigerant |
Equalizer |
Capillary(m) |
Connection Size Inlet(In) x outlet(In) |
RX2 |
R22 |
Internal |
1.5 |
3/8" x 1/2" |
REX2 |
External |
RN2 |
R134A |
Internal |
REN2 |
External |
RS2 |
R404A/R507 |
Internal |
RES2 |
External |
RF2 |
R12 |
Internal |
REF2 |
External |
RY2 |
R502 |
Internal |
REY2 |
External |
RZ2 |
R407C |
Internal |
REZ2 |
External |
Orifice:
Model |
Nominal Capacity/RT |
Nominal Capctiy/KW |
R22 |
R134A |
R404A/ R507 |
R12 |
R407C |
R22 |
R404A/R507 |
R12 |
R407C |
RX |
0.15 |
0.11 |
0.11 |
|
0.16 |
0.5 |
0.38 |
|
0.5 |
R0 |
0.3 |
0.25 |
0.21 |
0.2 |
0.3 |
1 |
0.7 |
0.7 |
1.1 |
R1 |
0.7 |
0.5 |
0.45 |
0.3 |
0.8 |
2.5 |
1.6 |
1 |
2.7 |
R2 |
1 |
0.8 |
0.6 |
0.5 |
1.1 |
3.5 |
2.1 |
1.7 |
3.8 |
R3 |
1.5 |
1.3 |
1.2 |
1 |
1.6 |
5.2 |
4.2 |
3.5 |
5.6 |
R4 |
2.3 |
1.9 |
1.7 |
1.5 |
2.5 |
8 |
6 |
5.2 |
8.6 |
R5 |
3 |
2.5 |
2.2 |
2 |
3.2 |
10.5 |
7.7 |
7 |
11.3 |
R6 |
4.5 |
3 |
2.6 |
3 |
4.9 |
15.5 |
9.7 |
10.5 |
16.7 |
Expansion Valve - V Series
Model |
Capacity/RT |
Inlet x outlet |
Equalizer |
Capillary Length (mm) |
@Evap.Temp -7ºC |
In |
FV-1-C |
1.09 |
1/4"X1/2" SAE |
Internal |
760 |
FV-1.5-C |
1.74 |
3/8"X1/2" SAE |
FV-2-C |
2.18 |
3/8"X1/2" SAE |
FV-2.5-C |
2.72 |
3/8"X1/2" SAE |
FVE-1-C |
1.09 |
1/4"X3/8" SAE |
External |
760 |
FVE-1.5-C |
1.74 |
3/8"X1/2" SAE |
FVE-2-C |
2.18 |
3/8"X1/2" SAE |
FVE-3-C |
3.49 |
3/8"X1/2" SAE |
FVE-5-C |
5.67 |
3/8"X1/2" SAE |
SVE-5-C |
5.67 |
1/2"X7/8" ODF |
External |
1500 |
SVE-8-C |
8.72 |
5/8"X7/8" ODF |
SVE-10-C |
10.90 |
5/8"X7/8" ODF |
SVE-15-C |
15.50 |
7/8"X1-1/8" ODF |
OVE-15-C |
15.50 |
7/8"X1-1/8" ODF |
OVE-20-C |
23.00 |
7/8"X1-3/8" ODF |
CP100 series Applied into Air-conditioner, Evaporating temperatue range: -25ºC~+10ºC
Model |
Capacity/RT |
Inlet x outlet |
Equalizer |
Capillary Length (mm) |
@Evap.Temp +4.5ºC |
In |
FVE-3-CP100 |
3.50 |
3/8"X1/2" SAE |
External |
760 |
FVE-5-CP100 |
5.70 |
3/8"X1/2" SAE |
SVE-5-CP100 |
5.70 |
1/2"X7/8" ODF |
1500 |
SVE-8-CP100 |
8.70 |
5/8"X7/8" ODF |
SVE-10-CP100 |
10.90 |
5/8"X7/8" ODF |
SVE-15-CP100 |
15.50 |
7/8"X1-1/8" ODF |
Remark:
Capacity on base of Liquid temperature 38ºC, Work with refrigerant R22;
Equalizer connector size are 1/4" SAE.
Expansion Valve - CGE Series
R22 Model |
Nominal capacity |
R134a Model |
Nominal capacity |
R407C Model |
Nominal capacity |
R404a Model |
Nominal capacity |
R410a Model |
Nominal capacity |
Connection size |
TR |
KW |
TR |
KW |
TR |
KW |
TR |
KW |
TR |
KW |
ODFxODF,In |
CGEX3 |
3.0 |
10.0 |
CGEN1.5 |
1.5 |
6.0 |
CGEZ2.5 |
2.5 |
9.0 |
CGES2.0 |
2.0 |
7.0 |
CGEL3.5 |
3.5 |
12 |
3/8x5/8, 1/2x5/8 |
CGEX4 |
4.0 |
14.0 |
CGEN2.5 |
2.5 |
8.0 |
CGEZ3.5 |
3.5 |
13.0 |
CGES2.5 |
2.5 |
9.0 |
CGEL4.5 |
4.5 |
16.0 |
1/2x7/8 |
CGEX6 |
6.0 |
20.0 |
CGEN3.5 |
3.5 |
12.0 |
CGEZ5 |
5.0 |
19.0 |
CGES4 |
4.0 |
14.0 |
CGEL6.5 |
6.5 |
24.0 |
1/2x5/8, 1/2x7/8, 5/8x7/8 |
CGEX7.5 |
7.5 |
27.0 |
CGEN4.5 |
4.5 |
17.0 |
CGEZ7 |
7.0 |
25.0 |
CGES5 |
5.0 |
18.0 |
CGEL9 |
9.0 |
32.0 |
5/8x7/8 |
CGEX11 |
11.0 |
38.0 |
CGEN7 |
7.0 |
24.0 |
CGEZ10 |
10.0 |
36.0 |
CGES7.5 |
7.5 |
26.0 |
CGEL13 |
13.0 |
45.0 |
5/8x7/8, 5/8x1-1/8 |
CGEX12 |
12.0 |
43.0 |
CGEN8 |
8.0 |
29.0 |
CGEZ12 |
12.0 |
42.0 |
CGES9 |
9.0 |
31.0 |
CGEL15 |
15.0 |
54.0 |
5/8x7/8, 5/8x1-1/8 |
CGEX15 |
15.0 |
54.0 |
CGEN10 |
10.0 |
37.0 |
CGEZ15 |
15.0 |
53.0 |
CGES11 |
11.0 |
39.0 |
CGEL19 |
19.0 |
68.0 |
5/8x1-1/8, 7/8x1-1/8 |
CGEX18 |
18.0 |
63.0 |
CGEN12 |
12.0 |
44.0 |
CGEZ18 |
18.0 |
62.0 |
CGES13 |
13.0 |
45.0 |
CGEL23 |
23.0 |
79.0 |
7/8x1-1/8, 7/8x1-3/8 |
Remark:
The Max working pressure: 46bar/667psig;
Max testing pressure: 51bar/740psig.
Please contact us freely to get more information or models.